For the electrical wirings please refer to the wiring diagram and technical characteristics of the panel model to be installed.
- Panel power supply must be on a dedicated line, and must be placed a device suitable for protection against indirect contacts upstream the line(differential interruptor).
- Do not fit power supply wiring and signal wiring (probes/sensors and digital inputs) in the same race ways or ducts.
- Do not use multi-polar cables in which there are wires connected to inductive/power loads or signaling wires (e.g. probes/sensors and digital inputs).
- Minimize the length of connector wires so that wiring does not twist into a spiral shape as this could have negative effects on the electronics.
- When it is necessary to make a probe/sensor extension, the wires must have a cross-section of at least 1mm2.
- All wiring must be of a cross-section suitable for relevant power levels. Insulation degree must be compatible with the applied voltages. Preferably use cables with insulator not propagating the flame and a low toxic smoke emission if interested by fire.