{ "@context": "https://schema.org", "@type": "HowTo", "name": "Installation Procedure for Blue Cold Condensing Unit - Immunity from Vibrations", "description": "Comprehensive engineering field manual outlining the physical placement, refrigeration piping connections, and wiring sequence for Condensing Unit - Immunity from Vibrations.", "totalTime": "PT4H", "estimatedCost": { "@type": "MonetaryAmount", "currency": "USD", "value": "0" }, "step": [ { "@type": "HowToStep", "url": "https://www.bluecoldref.com/installation-procedure/immunity-from-vibrations#step1", "name": "Unpacking and Structural Mounting", "text": "Inspect the unit chassis for shipping damage. Verify mounting point dimensions and lift the unit into place using structural hangers or support channels capable of handling the operating weight." }, { "@type": "HowToStep", "url": "https://www.bluecoldref.com/installation-procedure/immunity-from-vibrations#step2", "name": "Refrigeration Piping & Brazing", "text": "Route copper suction and liquid lines ensuring a continuous slope toward the compressor. Flow dry nitrogen through the lines while brazing joints to prevent internal oxide scaling." }, { "@type": "HowToStep", "url": "https://www.bluecoldref.com/installation-procedure/immunity-from-vibrations#step3", "name": "Pressure Leak Testing and Evacuation", "text": "Pressurize the system with dry nitrogen to the target design pressure and hold for 24 hours. Once leak-free, evacuate the system using a dedicated vacuum pump down to a deep vacuum below 500 microns." }, { "@type": "HowToStep", "url": "https://www.bluecoldref.com/installation-procedure/immunity-from-vibrations#step4", "name": "Electrical Connection and Pre-Commissioning", "text": "Connect the main three-phase power lines and link control sensors to the digital thermostat board. Verify fan rotation direction before introducing refrigerant." } ] }

Set Bar: HP 27 / LP 1
Difference Bar: HP 4 / LP 1
Pressure switch for Pump-down: this must be set considering that the compressor must not startup at intervals that are too close together (5 minutes at least). In these cases, we recommend the use of a timer for the compressor start delay.