Installation Procedure

Back

Condensing Unit - Operational Limits

When the Condensing Unit is being used, check with the final test data of the application product to see whether or not, the following standards are being maintained:

  1. Refrigerant used -> For Bitzer compressor with “Y” uses only R134a and R404a and without “Y” use R22
  2. Evaporating temperature range -> Please refer the Blue Cold technical sheet
  3. Discharge gas temperature -> Not exceed 115 °C (239 °F), This temperature should be measured at the surface of the heat-insulated discharge pipe at 150 mm distance from the shell surface
  4. Suction gas temperature -> Amount of refrigerant charge should be just sufficient to obtain at least 3 K of superheat to avoid any liquid flood-back
  5. Amount of refrigerant charged -> Amount of refrigerant charged should be just sufficient to obtain at least 3 K of superheat to avoid any liquid flood back. To prevent flood-back a proper accumulator must be installed in the suction pipe side according to the refrigerant charging amount
  6. ON/OFF frequency ->   The time between two successive compressor starts should be at least 5 min. The run time of compressor should be at least 3 min before stop
  7. Pipe stress -> The piping must be designed so that no damage will result from transporting of the product and the ON/OFF of the compressor. Recommendable tolerance of piping stress.
  1. At starting and stopping: 34.3N/mm2
  2. During operation:                 17.7N/mm2 
  1. Piping -> The unit pipes should be piped inside of discharge and suction pipes of the compressor
  2. Pipe clearance -> A clearance of at least 13mm must be left between the piping and active parts (compressor, fan, anti-resonance rubber, piping, etc.). A clearance of at least 10mm must be left between the piping and inactive parts

The unit should be designed to satisfy above operational standard and operational limit in any condition.

The following conditions are hazard-causing example in particular.

  1. In case of high or low supply voltage at the high ambient temperature (e.g. 43 °C)
  2. Flood-back at the low ambient temperature (e.g. -5 °C)
  3. In case of hard condition such as closing fan filter
  4. In case of transitional condition such as pull-down and defrost
  5. The phenomenon of abnormal low pressure to be caused by bad defrosts